Warehouse Sprinkler Shutdown in Tacoma: 6-Step Impairment Plan
Short answer: Name an impairment coordinator, tag the impaired system, notify your monitoring company, fire department, and insurer, start a fire watch if required, and book the repair at the same time. NFPA 25 Chapter 15 sets the framework.
1. Name an impairment coordinator
NFPA 25 requires the owner or a designated representative to assign an impairment coordinator who authorizes the shutdown and makes sure every step happens.
2. Tag the impaired system
Hang an impairment tag at each fire department connection and system control valve showing what is out of service.
3. Notify your alarm monitoring company
Tell them what is affected and how long it will be down, so signals are handled correctly.
4. Call the fire department
Notify Tacoma Fire Department Fire Prevention, or your fire district outside the city, and ask whether a fire watch is required, the patrol interval, and what log they want.
5. Book the fire watch and the repair together
High-piled storage in Port and Tideflats warehouses often relies on ESFR sprinklers. Every hour the system is down is exposure, so schedule the repair when you book the watch.
6. Restore, test, and notify
After repairs, test the system, remove the tags, and tell everyone you notified, including your insurer, that protection is back.
Sources: NFPA 25, Chapter 15: Impairments 路 Tacoma Fire Department, Fire Prevention
More guides: Hot Work Fire Watch in Tacoma: 6 Rules Before You Weld or Cut